Items | Specifications |
Maximum frequency | Vector control: 0~1000Hz |
V/F control: 0~1500Hz |
Matchable motor types | General asynchronous motor; Spindle asynchronous motor; |
Carrier frequency | 0.8 kHz ~ 16 kHz |
It can adjust the carrier frequency automatically according tothe loading characteristics. |
The resolution ratio of input frequency | Digital setting: 0.01Hz |
Simulating setting : Maximum frequency ×0.025% |
Control mode | Open-loop vector control (SVC) |
Close-loop vector control (FVC) |
V/F control |
Starting torque | G-Type machine : 0.5Hz/150%(SVC); 0Hz/180%(FVC) |
Speed regulating range | 1:100 (SVC) | 1:1000 (FVC) |
Precision of steady apeed | ±0.5%(SVC) | ±0.02%(FVC) |
Precision of torque control | ±5%(FVC) |
Overloading capacity | G-Type machine:150% of the rated current: 60s; 180% of the rated currnet: 3s |
Lifting of the Torque | Automatic torque has been improved; |
Manual torque has been improved by 0.1%~30.0% |
V/F curve | Three types of the V/F curve:linear type; multipoint type and N-th power type (1.2 powers, 1.4 powers, 1.6 powers, 1.8 powers and two powers of...) |
Curves of Acceleration and deceleration | Way of linear acceleration and deceleration; Four types of times for acceleration and deceleration; Time ranges of acceleration and deceleration: 0.0~6500.0s |
DC braking | The frequency of DC braking: 0.00Hz~ maximum frequency |
Time of braking: 0.0s~36.0s |
Current of braking action: 0.0%~100.0% |
Automatic rqgulation of voltage (AVR) | It can keep the output voltage in a state of constant automactically when the grid voltage changes. |
Function of fast current limiting | It can decrease the over-current fault on a maximum extent, thus protecting the normal operation of the spindle servo driver. |
|
Support for kinds of PG cards | Differential input PG card; Rotating transformer PG card, open collector |
Power dip ride through | The load feedback energy compensates the voltage reduction so that the AC drive can continue to run for a short time |
Overvoltage/overcurrent stall control | The current and voltage are limited automatically during the running process so as to avoid frequent tripping due to over voltage/over current |
Torque limit and control | It can limit the torque automatically and prevent frequent over current tripping during the running process. Torque control can be implemented in the FVC mode. |
Onboard multiple preset speeds | It implements up to 16 speeds via the simple PLC function or combination of X terminal states |