Item | Desctription |
Basic | Max. frequency | 0~599Hz |
Carrier frequency | 0.5kHz~16kHz |
The carrier frequency can be automatically adjusted according to load characteristics. |
Input frequency resolution | Digital setting:0.01Hz |
Analog setting: max.frequency×0.025% |
Control mode | Open-loop vector control(no PG) |
V/F control |
Start torque | G type:0.5Hz/150%(no PG); |
P type:0.5Hz/100% |
Adjust speed range | 1:100(no PG) |
Speed control accuracy | ±0.5%(no PG) |
Torque control accuracy | ±5%(FVC) |
Overload capacity | Type G: 150% rated current for 60 seconds; 180% rated current for 3 seconds |
Type P: 120% rated current for 60 seconds; 150% rated current for 3 seconds |
Torque boost | Automatic torque boost; Manual torque boost 0.1%~30.0% |
V/F curve | Three modes: Linear; Multi-point; Nth power V/F curves((1.2, 1.4, 1.6, 1.8, 2nd power)) |
V/F separation | 2 modes: Full separation, Semi-separation |
Acceleration/deceleration curve | Linear or S-curve acceleration/deceleration modes; four acceleration/deceleration times, ranging from 0.0 to 6500.0 s. |
Functions | DC braking | Braking frequency: 0.00Hz~max. frequency; |
Braking time: 0.0s~100.0s; |
Braking current: 0.0%~100.0% |
Jog control | Frequency range: 0.00Hz~50.00Hz; |
Acceleration/deceleration time: 0.0s~6500.0s |
Simple PLC, multi-speed operation | Up to 16 speed settings can be achieved via built-in PLC or control terminals |
Built-in PID control | This facilitates the implementation of closed-loop process control systems. |
Automatic voltage regulation (AVR) | The inverter automatically maintains a constant output voltage when the mains voltage changes. |
Overvoltage and overcurrent speed control | It automatically limits current and voltage during operation to prevent frequent overcurrent and overvoltage tripping. |
Fast current limiting function | It minimizes overcurrent faults, protecting the inverter for normal operation. |
Torque limiting and control | It automatically limits torque during operation to prevent frequent overcurrent tripping. |
Protection functions | Features include: motor short-circuit detection, input/output phase loss protection, overcurrent protection, overvoltage protection, undervoltage protection, overheat protection, and overload protection. |
Special features | Excellent performance | Utilizes high-performance current vector control technology for asynchronous motors. |
Fast rate limiting | Avoids frequent overcurrent faults in the frequency converter. |
Timed control | Timer control function: settable time range 0.0 min to 6500.0 min. |
Communication methods | Modbus RS-485, CAN, Profinet |
Runing | Command Source | The input methods—operation panel input, control terminal input, and serial communication port input—can be switched in multiple ways. |
Frequency Source | Ten frequency sources: digital input, analog voltage input, analog current input, and serial port input—can be switched in multiple ways. |
Auxiliary Frequency Source | 10 auxiliary frequency sources allow for flexible auxiliary frequency fine-tuning and frequency synthesis. |
Input Terminals | 6 digital input terminals. |
2analog input terminals support 0–10V voltage input or 4–20mA current input. |
Output Terminals | 2 relay output terminals. |
2 analog output terminals support 0–20mA current output or 0–10V voltage output |
environment | Altitude | Below 1000m (use at a lower setting above 1000m) |
Ambient Temperature | -10℃~+40℃ (use at a lower setting if ambient temperature is 40℃~50℃) |
Humidity | Less than 95%RH, no condensation |
Vibration | Less 5.9m/s²(0.6g) |
Storage temp. | -20℃~+60℃ |
Protective class | IP66 |